LonWorks central air-conditioning control collector

1.Product introduction
  GEC research and development this embedded product in order to satisfy the demand of central air-conditioning system access the LonWorks building control networks.This controller in Linux embedded platform based on ARM system empolder a controller conforms to the LonWorks standard, fully displayed the embedded product's superiority like cost lowly, run stably, maintain simply and so on.This controller contains a LonWorks interface module,provides condition data display and? control function to many (most reach 256) inside and outside hanging machine of the air conditioning,in addition, it also provided all the function of the central air conditioning ethernet controller.


Controller internal circuit outward appearance chart

2. Main performance index
  Hardware technical
index
  CPU: Uses Samsung ARM9 S3C2410, basic frequency 200M
  SDRAM: HY57V561620T 133MHZ, capacity 64M
  Nand Flash: Samsung K9F1208VOB 64M
  Interface:
  One Lonworks chip interface: run based on the Lonworks agreement, to integration with the BMS
  One 232COM mouth:To monitor start and operating condition of the equipment
  Two Ethernet-10M mouth: To send the gathered central air conditioning data message to remote?
  Four 485mouth: To gather the air conditioning data, at present each control collector can hang 64   airconditioning inside machine or 32 air conditioning outside machine , inside machine can not mix hang with outside machine
  One USB mouth: To debug; the official product can not use
  LCD and keystoke interface: to realize the control collector monitor in local
  Power supply: DC 12V
  According to the industry level application request, the design realizes 7*24*365 uninterrupted run

Software technical index
  The system provides the man-machine operation interface (LCD liquid crystal display) to carry on the air-conditioning system control in local for user, realiza control button function and display liquid crystal operation menu function.
  The system passively receives the command of Lonworks building management system for inquiry and control and give response;And not stop the circularly inquire the hanging air conditioning data and running status,and according to the premise-based to give the alarm forwardly to the building management system.
  The system provides the Lonworks intelligence building node control interface,realize docking the BMS system
  The system support necessary Lonworks standard object type and standard service
  The system supports the Lonworks object example automatic scan
  The system support 64 Midea air conditioning inside machine,32 outside machine most
  The system can discover the new air conditioning,and scan the air conditioning running status automatically.
  User may set the intervals of time gain data freely,realize dynamic gaining detailed data of commercial air conditioning and saving,time preserving the data to SDcard , the time preserving the data to be possible for a year.

3.function
  Local access: Provides 3.5 inch colored LCD touch screen or keystoke management controller.
Remote access: Built-in Web server, visit controller through Web browser, carriy on the remote management.
Intelligent work: need no enactment, automatically search the air conditioning equipment hang on the RS485 Bus.
  LonWorks: The system uses the LonWorks technology, uses the LonMarkstandard authentication, uses the nerve network technology,conveniently realizes the free topology, realizes the products' exchange? in different merchant.
  Data storage: Preserves the air conditioning performance data in the SD card for at least 1 year, for breakdown diagnosis.
  Centralized monitoring: The controller data is transmitted to the long-distance control center by the gathering, realize the remote the estate monitoring, the breakdown diagnosis, the short note control and so on.
  System capacity: Altogether 4 RS485 Bus interfaces may be use, each interface can connect no more than 64 air conditioning inside machine or 32 air conditioning outside machine or an air conditioning inside and outside machine control collector.
  Security: Use encryption user password mechanism guarantee the system far awary from external security attack.
  Stability: According to the industry level application request, the design realizes 7*24*365 uninterrupted run.